Each RADICAB wire is manufactured using 99.99% pure electrolytic grade, bright annealed bare copper with more than 100% conductivity for conductor, tested by ATCC NABL accredited laboratories. The wire is insulated with a Flame Retardant lead free (FR-LF) PVC compound with a high oxygen and temperature index, specially formulated and manufactured in house. Every wire meet the requirements of IS 694:2010 with latest amendments with improved fire performance properties.
Nominal Cross Sectional area of conductor | Number/Nom. Dia of cond. strands* | Thickness of Insulation (Nom) | Thickness of Insulation (Nom) | Max. Conductor Resistance at 20ºC | Current Rating AC | Packing | |
---|---|---|---|---|---|---|---|
sq. mm. | mm | mm | mm | Ohms/Km | Amps | Coils | |
0.5 | 16/0.20 | 0.6 | 2.20 | 39.00 | 4.00 | 24 | |
0.75 | 24/0.20 | 0.6 | 2.50 | 26.00 | 7.00 | 20 | |
1.0 | 32/0.20 | 0.6 | 2.70 | 19.5 | 12.00 | 20 | |
1.50 | 30/0.25 | 0.6 | 3.10 | 13.3 | 16.00 | 16 | |
2.50 | 50/0.25 | 0.70 | 3.70 | 7.98 | 22.00 | 12 | |
4.0 | 56/0.30 | 0.80 | 4.30 | 4.95 | 29.00 | 8 | |
6.0 | 84/0.30 | 0.80 | 4.80 | 3.3 | 37.00 | 4 | |
10.0 | 140/0.30 | 1.00 | 6.70 | 1.91 | 71.00 | 1 |